Structural Safety Evaluation of a Francis Hydro Turbine Model at Normal Operation Condition
Zhenmu Chen* ; Patrick Mark Singh* ; Young-Do Choi**,
*Graduate School, Department of Mechanical Engineering, Mokpo National University
**Department of Mechanical Engineering, Institute of New and Renewable Energy Technology Research, Mokpo National University

Correspondence to : † E-mail : ydchoi@mokpo.ac.kr

Funding Information ▼

Abstract

Francis turbine, as a widely used hydro turbine, is especially suited for the hydropower station with high hydraulic head. For such turbine generator units all around the world, the crack usually comes out after a long time use and the resulted accidents may cause huge losses. Moreover, it is better for the manufacture if we know the stress of each components of the hydro turbine. In order to verify the component structure integrity, fluid-structure interaction (FSI) is an effective method to calculate the stresses in the Francis turbine components. In this study, based on the fluid-structure coupling theory, the components structural analysis of a Ns=300 [m-kW-min-1] Francis hydro turbine model was done by using CFD and static structural analysis. The results show that the stresses caused by the hydraulic forces during the normal operation are safe and the high stress on the each component is much lower than the yield strength of the material.


Keywords: FSI analysis, Francis hydro turbine model, Numerical analysis
키워드: FSI 해석, 프랜시스 수차 모델, 수치해석

1. Introduction

Francis turbine, as a widely used hydro turbine, is especially suited for the hydropower station with high hydraulic head. For such turbine generator units all around the world, the crack usually comes out after a long time use and the resulted accidents may cause huge losses.

Hydropower has been a mainstream renewable energy technology for decades, and currently represents about 16 % of global electricity generation. However, while hydropower has been a steady constant in the energy supply scene, multiple energy resource combination is undergoing rapid and dramatic change.(1) Moreover, Francis turbines have been most widely used throughout the world because of its wide range of head and flow rate applications. It also provides a good efficiency near the 90% region. In most applications, it is used for high heads and flow rates.

Research on the technology of hydraulic turbine is continuously increasing with the development of water electricity. Z. Chen et al.(2) studied the effect of runner blade loading on the performance and internal flow of a Francis hydro turbine model. There are three different blade loadings conducted to compare the internal flow characteristics and performance. The conclusion is that the front loading achieves the best efficiency in comparison with the other loadings.

W. F. Li et al.(3) studied the pressure fluctuation reducing in draft tube of Francis turbine by numerical method. Three schemes have been put forward through numerical simulations, including air admission to the draft tube, water injection to the draft tube and adding a flow deflector in the draft tube, to solve the problem of high fluctuating output of the turbine caused by the resonance between the draft tube vortex frequency and the generator natural vibration frequency.

Z. Chen et al.(4) preformed Francis turbine blade design on the basis of port area and loss analysis successfully. The best efficiency of 92.6% was achieved by this method.

Moreover, there are some new applications of the Francis turbine runner for city water supply system to recycle the energy. C. Chen et al.(5) studied a feasibility and performance studies on the flow passage shape for an inline Francis hydro turbine. The inline casing is used instead of traditional spiral casing, which has a more compact-size and is very convenient for manufacture.

However, there is rare research force on the structural analysis of a Francis hydro turbine. If we know the stress of each components of the hydro turbine, it will be very helpful for the hydro turbine manufacture.

In order to verify the runner blade structure, fluid-structure interaction (FSI) is an effective method to calculate the stresses in the Francis turbine runner. Saeed et al.(6) found stress maxima in different parts of the runner by FSI method. Xiao et al.(7) investigated the dynamic stresses in a Francis turbine runner successfully based on FSI analysis. In this study, as the structural safety of the Francis hydro turbine is very important for the designers and manufacturers to guarantee the turbine, based on the fluid-structure coupling theory, the components structural analysis on a Ns=300 [m-kW-min-1] Francis hydro turbine model was done by using CFD and static structural analysis.


2. Francis Hydro Turbine Model and Numerical Method
2.1 Francis Hydro Turbine Model

The runner outlet diameter is De=350 mm. The number of the guide vanes are Zg=16, and the number of the blade is Zr=12. The design point of the Francis turbine model is at H=9 m for the effective head, Q=0.34 m3/s for the water flow rate and the rotational speed is N=900 min-1. The specific speed at the design point is Ns=300 [m-kW-min-1]. Fig. 1 shows the three-dimensional modeling view of the Francis hydro turbine model solid domain for the structural analysis. Fig. 2 shows the three-dimensional modeling view of the Francis hydro turbine model runner for the structural analysis. Table 1 shows the specifications of the Francis hydro turbine model in detail.


Fig. 1 
The 3D modeling of the Francis hydro turbine model solid domain for structural analysis


Fig. 2 
The 3D modeling of the Francis hydro turbine model runner for structural analysis

Table 1 
Design specifications of francis turbine model
Parameters Value
Effective head H 9 m
Flow rate Q 0.34 m3/s
Rotational speed N 900 min-1
Runner outlet diameter De 350 mm
Runner blade number Zr 12
Guide vane number Zg 16
Stay vane number Zs 16

2.2 Numerical Method

For the numerical analysis on the internal flow analysis of the Francis hydro turbine, a commercial code of ANSYS CFX(8) is adopted. Fig. 3 shows the numerical mesh for the CFD analysis at the center cross section plane. The fluid domain for the CFD analysis includes two leakage parts as shown in Fig. 3.


Fig. 3 
Numerical Mesh for the CFD analysis at the center cross section plane

According to previous study(9), the shear stress transport (SST) model has been applied to the analysis, which has been well known to estimate both separation and vortex occurrence on the wall of a complicated blade shape. The operating condition maintains the head at 9 m and the flow rate range varies according to the guide vane openings. The boundary conditions have been summarized in Table 2. For the structural analysis, the mesh dependence has been done as shown in Table 3. The peak stress with 2.0×106 element number is almost similar with that with 4.0×106 element number. Therefore, the final numerical mesh elements number of about 2.0×106 and nodes of about 3.5×106 for the total structure domain have been used as shown in Table 4. This table shows the detail for the grid number of each part of structure domain. Fig. 4 shows the numerical mesh of the Francis hydro turbine model for FSI structural analysis. The four legs and the runner shaft hole of the Francis hydro turbine model casing were set as support of fixed boundary condition as shown in Fig. 5. As the design point of the turbine operation is the key importance for the designer and manufacturer and the 100% guide vane opening of the turbine is the design point, in this study, CFD analysis and FSI analysis at the design point were conducted. The rotational velocity was applied for the runner. Moreover, the gravity is applied for the all components. The results obtained from the CFD analysis were imported for the FSI analysis as shown in Fig. 6, which is one-way FSI analysis. The mapping rate of CFD to static structural analysis was more than 90%.

Table 2 
Numerical methods and boundary conditions
Calculation type Steady state
Turbulence model SST model
Mesh type -Hexahedral
-Tetrahedral (Casing)
Total mesh number Nodes: 6.2×106
Elements: 6.3×106
Wall No slip
Inlet Total pressure
Outlet Static pressure

Table 3 
Mesh independence
Total element number Peak stress (MPa)
1024691 40.1
2010586 44.7
4012092 45.0

Table 4 
Mesh and components weight information
Components Nodes Elements Weight [N]
Casing 2106681 1199294 4041.5
Cover 310183 193620 1175.0
Stay vane 170791 32004 114.6
Runner 588080 370373 376.3
Draft tube 343980 215295 961.3
Total 3519715 2010586 6668.9


Fig. 4 
Numerical mesh of the francis hydro turbine model for FSI structural analysis


Fig. 5 
Boundary condition for the francis hydro turbine model FSI structural analysis


Fig. 6 
Imported each component pressure load from CFD to structure analysis


3. Results and Discussion
3.1 Performance Characteristic Curves

To obtain the hill chart of the Francis hydro turbine model, all the flow rate and rotation speed are normalized to unit flow and unit speed. The normalization of units is calculated by the following equations:

N11=ND1H(1) 
Q11=QD12H(2) 
η=TωρgHQ(3) 

where N11 is the unit speed, Q11 is the unit flow, N is the rotational speed, D1 is the diameter of runner, Q is the flow rate, H is the head of turbine, T is the torque, ω is the rotational speed of runner. The efficiency of the hydro turbine model is calculated by the Eq (3).

The hill chart of the Francis turbine model by CFD analysis is shown in Fig. 7. The efficiency in the hill chart is normalized to η/ηmax.. It can be seen that the high efficiency ratio of 0.99 locates at the guide vane opening from 28 mm to 34 mm. Therefore, the operation range of this turbine with high performance is relatively wide.


Fig. 7 
Hill chart of the Francis hydro turbine model by CFD analysis

3.2 FSI Analysis Results

Fig. 8 shows the pressure contours from the CFD analysis. The pressure calculated by the CFD analysis at the design flow rate condition is imported for the pressure loading on the casing, stay vane, cover and runner surface.


Fig. 8 
The pressure contours from CFD analysis

Fig. 9 to 12 shows the FSI analysis results for the Francis hydro turbine model. The stress on the casing is relatively higher than that on the other components. The maximum stress of around 44.7 MPa is found on the one of the legs of the turbine casing, where is the connection point between the leg supporter and the casing of the Francis hydro turbine. The material of steel is used for the casing. The property of the steel is shown in Table 5 in detail. The tensile yield strength of the steel is 250 MPa. Therefore, the stress of the casing is much lower than the yield strength of the steel, and thus the casing the safe under this condition.


Fig. 9 
The stress distribution on the casing


Fig. 10 
The stress distribution on the covers


Fig. 11 
The stress distribution on the stay vanes


Fig. 12 
The stress distribution on the runner

Table 5 
Material properties of steel
Property Steel
Young’s modulus (MPa) 2×105
Poisson’s ratio 0.3
Tensile yield strength (MPa) 250
Compressive yield strength (MPa) 250

The maximum stress on the cover is only around 3.2 MPa, which is very low stress for the cover part. The stress distribution on the cover is relatively uniform. The material of the cover is steel as well. The structure of the cover is quite safe as the maximum stress on the cover is much lower than the yield strength of steel.

The stress distribution on the stay vanes is observed in Fig. 11. The stay vanes are welded on the casing to support the casing. Therefore, it is necessary to investigate the stress on the connection points between stay vanes and casing for manufacture. Maximum stress point of 27 MPa is found on the one of the stay vanes, where is the tongue part of the casing. The maximum stress locates on the trailing edge of the stay vane.

The runner of the Francis hydro turbine is the key component of the turbine unit. As the runner blade shape is very complex, the runner blade and the hub part are manufactured by the milling machine together. The shroud is welded together with runner afterward. The stress is examined that the maximum stress is only 22 MPa on the connection point between blade and hub. In comparison with the yield stress of the steel, the stress on the runner is quite lower. The runner is quite safe under the normal turbine operation condition. The summary of each component stress is shown in Fig. 13 to compare with the yield stress of steel.


Fig. 13 
Comparison of each component stress to the yield stress of steel


4. Conclusion

In order to verify the component structure integrity, FSI is an effective method to calculate the stresses in the Francis turbine components. The pressure calculated by CFD analysis at the design flow rate is imported for the pressure loading on the casing, stay vane, cover and runner surfaces for FSI analysis. The highest stress of 41 MPa is found on the casing component, where is connection part between the leg supporter and the casing of the Francis hydro turbine. The stress on the casing and other components are quite lower than the yield stress of the steel, which means the turbine is quite safe under the normal turbine operation condition.


Acknowledgments

This work was supported by the New and Renewable Energy of the Korea Institute of Energy Technology Evaluation and Planning (KETEP) grant funded by the Korea government Ministry of Trade, Industry and Energy (No. 20163010060350).


References
1. IHA central office, (2016), “2015 Hydropower Status Report,” International Hydropower Association.
2. Chen, Z., and Choi, Y. D., (2016), “A Study on the Effect of Port Area of Blade on the Performance of Francis Hydro Turbine”, The KSFM Journal of Fluid Machinery, 19(1,), p5-10.
3. Li, W. F., Feng, J. J., Wu, H., Lu, J. L., Liao, W. L., and Luo, X. Q., (2015), “Numerical Investigation of Pressure Fluctuation Reducing in Draft Tube of Francis Turbines”, International Journal of Fluid Machinery and Systems, 8(3), p202-208.
4. Chen, Z., Singh, P. M., and Choi, Y. D., (2016), “Francis Turbine Blade Design on the Basis of Port Area and Loss Analysis”, Energies, 9(3), p164.
5. Chen, C., Singh, P. M., Inagaki, M., and Choi, Y. D., (2015), “A Feasibility Study on the Flow Passage Shape for an Inline Francis Hydro Turbine”, The KSFM Journal of Fluid Machinery, 18(2), p5-13.
6. Saeed, R. A., Galybin, A. N., and Popov, V., (2010), “Modeling of Flow-Induced Stresses in a Francis Turbine Runner”, Advances in Engineering Software, 41(12), p1245-1255.
7. Xiao, R., Wang, Z., and Luo, Y., (2008), “Dynamic Stresses in a Francis Turbine Runner Based on Fluid-Structure Interaction Analysis”, Tsinghua Science & Technology, 13(5), p587-592.
8. ANSYS Inc, (2013), “ANSYS CFX Documentation,” Ver. 13.
9. Le, V., Chen, Z., and Choi, Y. D., (2016), “A Study on CFD Analysis Methods using Francis-99 Workshop Model”, The KSFM Journal of Fluid Machinery, 19(5), p20-27.